°í°´¼¾ÅÍ

Á¦Ç°Ä«Å×°í¸®

¿Â¶óÀι®ÀÇ ±â¼úÀÚ·á½Ç ¿À½Ã´Â±æ
  > Àü±âÀüÀÚ°èÃø±â > ¹èÀü¹Ý½ÃÇè¿ë > --->µðÁöÅиÖƼ¹ÌÅÍ

--->µðÁöÅиÖƼ¹ÌÅÍ

À̹ÌÁö detail
Digital Multimeter(HIOKI/4254,55,56), 0.3%
  • Á¦Á¶»çHIOKI
  • ¸ðµ¨¸íDT4254, DT4255, DT4256
  • ÁÖ¿ä±â´É AC/DC, Àü¾Ð, Àü·ù, ÀúÇ× ÃøÁ¤±â´É
»óÇ°»ó¼¼Á¤º¸




 

 

 

The Hioki DT4200 Digital Multimeter Series consist of a complete lineup of 9 models ranging from professional to industrial to pocket meters, delivering a super fast response rate and safety features that take electrical testing to a higher level. The DT4254 is a voltage measurement only model designed for measuring photovoltaic modules and other high-voltage targets up to 1700 V DC. Key Features • High-voltage measurement up to 1700 V DC • ¡¾0.3% DC V basic accuracy, wide 40 Hz to 1 kHz AC V frequency characteristics • Low-pass filter (100 Hz/ 500 Hz) cuts high harmonics (when measuring inverter fundamental waveforms) • Connect to PC with USB communication function (optional) • Broad -25¡ÆC (-13¡ÆF) to 65¡ÆC (149¡ÆF) operating temperature range CAT IV 600 V, CAT III 1000 V

 


¡á Basic specifications (Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year)Regarding DMM Accuracy Due to the many ranges and functions available in a DMM, only the basic accuracy is indicated for reference. Please refer to the individual catalogs for detailed accuracy information.


DC Voltage600.0 mV to 1500 V
5 ranges, Basic accuracy: ¡¾0.3 % rdg. ¡¾3 dgt.
AC Voltage6.000 V to 1000 V, 4 ranges, Frequency characteristics: 40 Hz to 1 kHz
Basic accuracy 40 - 500 Hz : ¡¾0.9 % rdg. ¡¾3 dgt. (True RMS, crest factor 3)
AUTO AC/DCVYes
ResistanceN/A
DC CurrentN/A
From 4 to 20mA Percentage conversion displayN/A
AC Current (use with Clamp on probes) N/A
Temperature (thermocouples)N/A
Voltage detectionHi: AC40 V to 600 V, Lo: AC80 V to 600 V
C (capacitance)N/A
Frequency99.99 Hz to 99.99 kHz, 4 ranges (limited by the minimum detectable voltage),
Basic accuracy: ¡¾0.1 % rdg. ¡¾1 dgt.
Continuity checkN/A
Diode testN/A
Other functionsFilter function, Display value hold, Auto hold, Max/Min/Average value display, Relative display, Auto-power save, USB communication (option)
DisplayMain and Sub displays: 4-digits LCD, max. 6000 digits, bar graph
Display refresh rates5 times/s (Capacitance measurement: 0.05 to 5 times/s, depending on measured value, Frequency: 1 to 2 time/s)
Power supplyLR03 alkaline batteries ¡¿4, Continuous use: 130 hours (backlight OFF)
Dimensions and mass84 mm (3.31 in)W ¡¿ 174 mm (6.85 in)H¡¿ 52 mm (2.05 in)D,
390 g (13.8 oz) (including batteries and holster)
AccessoriesTest lead L9207-10 ¡¿1, Holster ¡¿1, Instruction manual ¡¿1, LR03 alkaline battery ¡¿4