°í°´¼¾ÅÍ

Á¦Ç°Ä«Å×°í¸®

¿Â¶óÀι®ÀÇ ±â¼úÀÚ·á½Ç ¿À½Ã´Â±æ
  > Àü±âÀüÀÚ°èÃø±â > ¹èÀü¹Ý½ÃÇè¿ë > --->Àý¿¬½ÃÇè±â

--->Àý¿¬½ÃÇè±â

À̹ÌÁö detail
Digital Insulation Tester(KYORITSU/3125A), 5000V/1000G§Ù
  • Á¦Á¶»çKYORITSU
  • ¸ðµ¨¸íKEW3025A, 3125A
  • ÁÖ¿ä±â´É °íÀý¿¬ÀúÇ×½ÃÇè±â
»óÇ°»ó¼¼Á¤º¸


 

 

High Voltage Insulation Testers

KEW 3025A

NEW

KEW 3025A
CE
AutoDischarge
High Voltage Insulation Tester
• Short-Circuit Current up to 1.5mA
• Diagnosis Function of PI and DAR
• Newly-designed alligator clip
• It comes with a tough hard case
• Filter function reduces noise interference for obtaining stable measurement
• Large display with Bar Graph indication and backlight
• Live voltage warning
• Safety standard IEC 61010-1 CAT IV 300V / CAT III 600V
(Photo: 3125A)
  • CAT4¡¡300V CAT3¡¡600V DCACV Backlight AutoPowerOff

  • 250V 500V 1000V 2500V

Insulation resistance

Rated voltage250V500V1000V2500V
Accuracy0.0 - 100.0M¥Ø 0.0 - 99.9M¥Ø
80 - 1000M ¥Ø  
0.0 - 99.9M¥Ø 
80 - 999M¥Ø
0.80 - 2.00G  ¥Ø
 0.0 - 99.9M¥Ø 
 80 - 999M¥Ø
 0.80 - 9.99G¥Ø 
 8.0 - 100.0G¥Ø
¡¾5%rdg¡¾3dgt¡¾5%rdg¡¾3dgt¡¾5%rdg¡¾3dgt¡¾5%rdg¡¾3dgt
Short circuit current1.5mA
Output voltage 
 Accuracy¡¾10%-10 - +20%0 - +20%
Monitor¡¾10%rdg¡¾20V

Voltage measurement

Measuring rangeAC: 30 - 600V (50/60Hz), DC: ¡¾30 - ¡¾600V
Accuracy¡¾2%rdg¡¾3dgt

General

Applicable standardsIEC 61010-1, 61010-2-030 CAT ¥³ 300V / CAT ¥² 600V Pollution degree 2,
IEC 61010-031, IEC 61326-1, 2-2
Power sourceDC12V : LR14/R14 ¡¿ 8pcs
Dimensions177 (L) ¡¿ 226 (W) ¡¿ 100 (D) mm
300 (L) ¡¿ 315 (W) ¡¿ 125 (D) mm (Hard case)


Weight3025A: 1.7kg approx. (including batteries)
4kg approx. (including accessories)
Included Accessories7165A (Line probe: 3m), 7264 (Earth cord: 3m), 7265 (Guard cord: 3m),
8019 (Hook type prod), 9180 (3025A Hard case), 9181 (3125A Hard case),
LR14 (Alkaline battery size C) ¡¿ 8, Instruction manual



Optional Accessories7168A (Line probe with alligator clip: 3m),
7253 (Longer line probe with alligator clip: 15m),
8302 (Adaptor for recorder)
 

 

 

High Voltage Insulation Testers

KEW 3125A

NEW

KEW 3125A
CE
AutoDischarge
• Insulation Resistance up to 1T¥Ø
• Short-Circuit Current up to 1.5mA
• Wide Test Voltage from 250V to 5000V
• Diagnosis Function of PI and DAR
• Newly-designed alligator clip
• It comes with a tough hard case
• Filter function reduces noise interference for obtaining stable measurement
• Large display with Bar Graph indication and backlight
• Live voltage warning
• Safety standard IEC 61010-1 CAT IV 300V / CAT III 600V
  • CAT4¡¡300V CAT3¡¡600V DCACV Backlight AutoPowerOff
  • 250V 500V 1000V 2500V 5000V

Insulation resistance

Rated voltage250V500V1000V2500V5000V
Accuracy0.0 - 100.0M¥Ø 0.0 - 99.9M¥Ø
80 - 1000M ¥Ø  
0.0 - 99.9M¥Ø 
80 - 999M¥Ø
0.80 - 2.00G  ¥Ø
 0.0 - 99.9M¥Ø 
 80 - 999M¥Ø
 0.80 - 9.99G¥Ø 
 8.0 - 100.0G¥Ø
0.0 - 99.9M¥Ø
80 - 999M¥Ø
0.80 - 9.99G¥Ø
8.0 - 99.9G¥Ø
80 - 1000G¥Ø
¡¾5%rdg¡¾3dgt¡¾5%rdg¡¾3dgt¡¾5%rdg¡¾3dgt¡¾5%rdg¡¾3dgt¡¾5%rdg¡¾3dgt
¡¾20%rdg
(100G¥Ø or more)
Short circuit current1.5mA
Output voltage  
Accuracy¡¾10%-10 - +20%0 - +20%
Monitor¡¾10%rdg¡¾20V

Voltage measurement

Measuring rangeAC: 30 - 600V (50/60Hz), DC: ¡¾30 - ¡¾600V
Accuracy¡¾2%rdg¡¾3dgt

General

Applicable standardsIEC 61010-1, 61010-2-030 CAT ¥³ 300V / CAT ¥² 600V Pollution degree 2,
IEC 61010-031, IEC 61326-1, 2-2
Power sourceDC12V : LR14/R14 ¡¿ 8pcs
Dimensions177 (L) ¡¿ 226 (W) ¡¿ 100 (D) mm
300 (L) ¡¿ 315 (W) ¡¿ 125 (D) mm (Hard case)
Weight3125A: 1.9kg approx. (including batteries)
4kg approx. (including accessories)
Included Accessories7165A (Line probe: 3m), 7264 (Earth cord: 3m), 7265 (Guard cord: 3m),
8019 (Hook type prod), 9180 (3025A Hard case), 9181 (3125A Hard case),
LR14 (Alkaline battery size C) ¡¿ 8, Instruction manual
Optional Accessories7168A (Line probe with alligator clip: 3m),
7253 (Longer line probe with alligator clip: 15m),
8302 (Adaptor for recorder)

Accessories/Optional Accessories /Related Products