3 Phase Relay Test Set(doble/F6150)
  • Á¦Á¶»çdoble
  • ¸ðµ¨¸íF6150
  • ÁÖ¿ä±â´É 3»ó °èÀü±â ½ÃÇè±â
»óÇ°»ó¼¼Á¤º¸





VERSATILE SOLUTION FOR DEVICES AND SCHEMES 

The Doble F6150e is a versatile protective relay tester for testing relays and schemes.

This power system simulator performs the simplest through the most complex tests. Meeting all your protective relay testing needs, the F6150e is available in different configurations.

Whether you need to test a specific component or test an entire scheme, the F6150e is the proven solution to assess protection system performance.

 

FEATURES
• Performs standard relay calibration and verification testing of high burden and microprocessor relays
• Analog testing of 1A and 5A protection devices
• Performs state simulation and transient testing
• Tests 0.2-class metering CTs and transducers
• Implements end-to-end testing of communications-based schemes with GPS time syncing
• Maximum of 12 Sources (six voltage, six current) configurable for bench testing and proof-of-concept testing for complicated relaying schemes
• Delivers full VA power with resistive, inductive and capacitive loads at maximum current rating (6x35, 3x70, 1x210 amps)
• Wi-Fi capable (optional)
• Control all sources from a tablet device for basic, manual protection testing​

 

BENEFITS
• Select from a number of instrument models that feature varying power testing and budgetary requirements. 

• Rugged construction and proven state-of-the art design provide laboratory accuracy with uncompromising field performance
• Convenient front-panel display indicates active voltage/current amplitudes and phase values during testing
• High-precision measurements for energy meter and transducer testing​

  

 Doble F6150 Specifications: 

Input Power90-264 VAC
47-63 Hz
Source Configurations
Voltage Source
Power and Range3 X 150 VA 75, 150, 300V
6 X 75 VA 75, 150 V

Each voltage source can be configured as a high power, low current range source to test high impedance ground/earth fault relays.

Power and Range3X150 VA    0.5, 1, 1.5 A
6X75 VA    0.5, 1 A
1X450 VA   1.5, 3, 6 A
Accuracy< 0.02% typical
Current Source
Power and Range3 X 150 VA    7.5, 15, 30 A
6 X 75 VA    7.5, 15 A
1 X 450 VA   7.5, 15, 22.5, 30, 45, 90 A
Accuracy< 0.02% Typical

Each current source can be used in a transient mode which provides 50% more power at 2X current range

Phase Angle0 to + 359.9¡Æ (Lead)
0 to -359.9¡Æ (Lag)
Accuracy< 0.1¡Æ typical
Frequency
RangeDC to 3 kHz
Accuracy0.5 PPM
Number of Logic Inputs8
Number of Logic Outputs8
Operating
Temperature0¡Æ to 50 ¡ÆC / 32 ¡Æ 122¡ÆF
EnclosureHigh impact, molded, flame retardant ABS - Meets National Safe Transit Association testing specification No. 1A for immunity to severe shock and vibration
Dimensions15 X 9.5 X 18 inches
Weight37.5 lb