°í°´¼¾ÅÍ

Á¦Ç°Ä«Å×°í¸®

¿Â¶óÀι®ÀÇ ±â¼úÀÚ·á½Ç ¿À½Ã´Â±æ
  > Àü±âÀüÀÚ°èÃø±â > ¹èÀü¹Ý½ÃÇè¿ë > --->ºÎÇϽÃÇè±â

--->ºÎÇϽÃÇè±â

À̹ÌÁö detail
Primary Current Injection Tester(Vanguard/PCI-600), 1000A/1.0%
  • Á¦Á¶»çVanguard
  • ¸ðµ¨¸íPCI-600
  • ÁÖ¿ä±â´É ºÎÇϽÃÇè±â
»óÇ°»ó¼¼Á¤º¸

  

 

 

 

 

  

 

 

 

 

PCI-600 Primary Current Injection Source

The VIC Model PCI-600 is a programmable, high-current source that is designed specifically for utility-substation applications. This alternating current(ac) test device is used primarily for injection testing of protective relays. This same device can also be used for testing thermal, magnetic and solid-state motor-protection relays and molded-case circuit breakers. The PCI-600 is versatile and can also be used in many other applications that require a high-current source.

 

  • Results displayed on a 4-line by 20-character backlit LCD
  • Test currents from 10 to 600 amperes
  • Also has an external-current input (0-10 A)
  •  

     

     

    Technical Specifications  

    TYPE

    10 – 600 Amp current source

    PHYSICAL SPECIFICATIONS

    16.8¡±W x 12.6¡±H x 10.6¡± D (42.6 cm by 32.0 cm by 27 cm); Weight: 46lbs (21kg)

    INPUT POWER

    100 – 120 Vac or 200 – 240 Vac (factory pre-set), 50/60 Hz

    INTERNAL CURRENT METER

    100 mA – 1000 A; Accuracy: 1% of reading, ¡¾20 mA

    MEASURING METHOD

    Isolated CT

    EXTERNAL METER RANGE

    10 mA – 10 A; Accuracy: 1% of reading, ¡¾2 mA

    MEASURING METHOD

    Isolated CT

    TIMER READING RANGE

    1 ms – 2 hours; Accuracy: 0.1% of reading ¡¾1ms

    TIMER STOP INPUT

    Voltage input (24 – 300 V, DC or peak AC), dry-contact input, or removal of primary current

    COMPUTER INTERFACE

    RS-232C port (19,200 baud) for factory calibration and diagnostics

    SAFETY

    Designed to meet IEC61010 (1995), UL 61010A-1, CSA-C22.2 standards

    ENVIRONMENT

    Operating: -10¢ªC to 50¢ª C (15¢ªF to +122¢ª F); Storage: -30¢ª C to 70¢ª C (-22¢ªF to +158¢ª F)

    CABLES

    10-foot #1/0 AWG test leads, power cord, ground cable

    OPTIONS

    Transportation case

    WARRANTY

    One year on parts and labor

    Specifications are valid at nominal voltage and ambient temperature of +25¢ªC (+77¢ªF).
    Last updated on February 13, 2009