This easy-to-use, battery-operated test set measures dissipation factor (tan ¥ä), power factor (cos ᵠ), capacitance, inductance, quality factor, and power (watts) which can be converted to 10kV. Built to stand up to the harsh conditions of field testing, this instrument provides reliable test results in any situation.
Range | Resolution | Accuracy | |
Dissipation Factor tan ¥ä | 0¡¦0.1 | 1 x 10-5 | ¡¾ 0.5% Rdg ¡¾ 1 x 10-4 |
0.1¡¦1 | 1 x 10-4 | ¡¾ 0.5% Rdg ¡¾ 1 x 10-4 | |
>1 | 3 Digits | ¡¾ 0.5% Rdg | |
Power Factor cos ᵠ | 0 ¡¦ 0.1 | 1 x 10-5 | ¡¾ 0.5% Rdg ¡¾ 1 x 10-4 |
0.1 ¡¦ 1 | 1 x 10-4 | ¡¾ 0.5% Rdg ¡¾ 1 x 10-4 | |
Capacitance @60 Hz | 0.00pF to 1.1 µF @ 500V | 0.01pF or 5 Digits | ¡¾ 0.3% Rdg ¡¾ 0.3pF |
0.00pF to 212 nF @ 2.5kV | 0.01pF or 5 Digits | ¡¾ 0.3% Rdg ¡¾ 0.3pF | |
Capacitance @50 Hz | 0.00pF to 1.3 µF @ 500V | 0.01pF or 5 Digits | ¡¾ 0.3% Rdg ¡¾ 0.3pF |
0.00pF to 254 nF @ 2.5kV | 0.01pF or 5 Digits | ¡¾ 0.3% Rdg ¡¾ 0.3pF | |
Test Voltage | Up to 2500V rms (45 ¡¦ 400 Hz) | 1V | ¡¾ 0.5% Rdg ¡¾ 1V |
Test Current | Up to 200 mArms | 0.1 µA or 4 Digits | ¡¾ 0.3% Rdg ¡¾1µA |
Output Power | 0 ¡¦ 500VA | ||
Output Frequency | 10 Hz ¡¦ 400 Hz (Step 0.5 Hz) | 0.1 Hz | ¡¾ 0.01% |
HV Cable – 10m (32 ft.)