°í°´¼¾ÅÍ

Á¦Ç°Ä«Å×°í¸®

¿Â¶óÀι®ÀÇ ±â¼úÀÚ·á½Ç ¿À½Ã´Â±æ
  > Àü±âÀüÀÚ°èÃø±â > Àü±â°ø»ç¿ë

Àü±â°ø»ç¿ë

À̹ÌÁö detail
Non-contact Voltage Tester
  • Á¦Á¶»çHIOKI
  • ¸ðµ¨¸í3258
  • ÁÖ¿ä±â´É Non-contact, 600V
»óÇ°»ó¼¼Á¤º¸

 

 

 

 

¡á Basic specifications (Accuracy guaranteed for 1 year, Post-adjustment accuracy guaranteed for 1 year)Regarding DMM Accuracy Due to the many ranges and functions available in a DMM, only the basic accuracy is indicated for reference. Please refer to the individual catalogs for detailed accuracy information.

Measurement parameterAC voltage (AC potential bridge)
Objects of measurementInsulated conductors (IV or CV equivalent, min. 100 mm©÷ x-section), metal conductors Note: Not usable on shielded conductors
Measurement range420.0V/ 600V AC (Auto)
Measurement valuesTrue RMS




Max. rated voltage to earth600V AC rms
Influence of adjacent wiring¡¾5% rdg. or less
Temperature characteristics0.05 % rdg./ ¡ÆC
DisplayDigital LCD, max. 4200 digit (zero suppress at 10 digits or less)
Display refresh rateApprox. once every 0.6 seconds
Display response2.4 s or less
FunctionsData hold function, auto-power off, low battery warning
Power supplyLR6 (AA) alkaline battery ¡¿6, Continuous use: 14 hr (Power ON, no measurement), or 1-minute measurements for 1000 times, or 5-minute measurements for 200 times
Dimensions and mass51mm (2.01in) W ¡¿ 275mm (10.83in) H ¡¿ 37.5mm (1.48in) D (one probe), 670g (23.6oz)
AccessoriesInstruction manual ¡¿1, LR6 (AA) alkaline battery ¡¿6, Soft carrying case ¡¿1