À̹ÌÁö detail
Earth Clamp Tester (KYORITSU/4200,02), 30A/1.5%
  • Á¦Á¶»çKYORITSU
  • ¸ðµ¨¸í4200, 4202
  • ÁÖ¿ä±â´É Ŭ·¥ÇÁÇü Á¢ÁöÀúÇ×ÃøÁ¤
»óÇ°»ó¼¼Á¤º¸




 

 

 

Earth Clamp Testers

KEW 4202

Various useful functions are available on Android devices using Bluetooth communication
• Real time measurements can be transferred, shown and saved on Android device (up to 100 measurements)
• Saved data includes measurement, GPS location and date & time Easy to check on map "When" and "Where" the measurement was made
• Comparator function on Android device informs when the measured value is lower/higher than the preset value

Earth /Ground resistance and Leakage current measurement functions
• The earth resistance from 0.05 to 1500 ¥Ø can be measured without the auxiliary earth spikes in multi-earthing systems
• True RMS leakage or phase current readings from 0.1mA to 30.0A provides vital additional information in earthing networks
• Filter function offers increased immunity to electrical noise and a Noise mark appears in excessively high noisy environments
  • TRUE RMS ¥õ32 Backlight Bluetooth

Free Android software "KEW smart 4202"
is available on "Google Play Store"(*)


• Supporting Android ver. 3.0 - 6.0
• WVGA (800 ¡¿ 480) resolution or higher
• GPS function

(*)Please search "KEW Smart" in Google Play Store.
Communication charge may be incurred separately to download application.

Earth resistance Auto range20.00/200.00/1500¥Ø
¡¾1.5%¡¾0.05¥Ø(0.00 - 20.99¥Ø)
¡¾2%¡¾0.5¥Ø(16.0 - 99.9¥Ø)
¡¾3%¡¾2¥Ø(100.0 - 209.9¥Ø)
¡¾5%¡¾5¥Ø(160 - 399¥Ø)
¡¾10%¡¾10¥Ø(400 - 599¥Ø)
AC current (50Hz/60Hz) Auto rangeValues are displayed, but accuracy isn't guaranted(600 - 1580¥Ø)
100.0/1000mA/10.00/30.0A
¡¾2%¡¾0.7mA(0.0 - 104.9mA)
¡¾2%(80mA - 31.5A)
Operating indicationEarth resistance function :
Constant voltage injection
Current detection (Frequency : Approx.2400Hz)
Dual Integration
AC current function : Successive approximation
Over-range indication"OL"is displayed when input exceeds the upper limit of a measuring range
Response timeApprox. 7 seconds (Earth resistance)
Approx. 2 seconds (AC current)
Sample rateApprox. 1 times per second
Communication InterfaceBluetooth Ver2.1 + EDR Class2
Current consumptionApprox. 50mA (max.100mA)
Measurement timeApprox.5 hours (when R6 is used) Approx. 21 hours (when LR6 is used)
Auto power-offTurns power off about 10 minutes after the last button operation.
Conductor sizeApprox.¨ª32mm
Applicable standardsIEC 61010-1 CAT ¥³ 300V Pollution degree2
IEC 61010-2-032, IEC 61326 (EMC)
Power sourceDC6V : R6(sizeAA manganese battery) x 4
or LR6 (sizeAA alkaline battery) x 4
Dimensions246(L)¡¿120(W)¡¿54(D)mm
WeightApprox. 780g (including batteries)
Included AccessoriesLR6 x 4, Instruction manual
8304 (Resister for operation check)
9167 (Carrying case[Hard])