Multifunction Tester(KYORITSU/6016), 200§Ì/2.0%
  • Á¦Á¶»çKYORITSU
  • ¸ðµ¨¸íKEW6016
  • ÁÖ¿ä±â´É ¿¬¼Ó¼º, Àý¿¬, ÀÓÇÇ´ø½º, Á¢Áö, »ó, Àü¾Ð ÃøÁ¤
»óÇ°»ó¼¼Á¤º¸




 

 

Multi Function Testers

KEW 6016 

Continuity Measurement
Continuous testing can be carried out by use of the test button lockdown feature. A selectable buzzer gives instantaneous indication of continuity. Null facility eliminates the test lead resistance from the results, the nulled value is retained even if the instrument is switched off. Live circuit warnings are given by a flashing LED, buzzer and indication on the display.

Insulation Measurement
Three selectable test voltages 250V, 500V and 1000V. An auto-discharge function ensures that circuits are not hazardous after testing. A red LED gives warning of high voltage output during testing and discharging of the circuit. In case of connecting to a live circuit, a live circuit warning is given by flashing LED, buzzer and indication on the display.

Loop Impedance Measurement
A patented (ATT) low current loop impedance test enables high accuracy loop measurements and quick testing without tripping RCD's.
A high current alternative is selectable for even higher accuracy and instantaneous results. The subsequent test will default to the low current test, this saves any inadvertent tripping of the RCD. The KEW 6016 allows also for phase to phase loop tests.

 

 

PSC / PFC Measurement
The Prospective Short Circuit Current (PSC) and Prospective Fault Current (PFC) are automatically calculated and shown on the display. As loop testing, the function has low and high test current options with the default to low current to avoid inadvertent tripping of RCDs.

RCD Measurement
The KEW 6016 has a comprehensive RCD test feature for RCD type AC (Alternative Currents), RCD type A (Pulsating Direct Currents), General and Selective (delayed).

Measures at 1/2x, 1x, 5x of nominal RCD current. It also has Ramp Test and Auto test where all results are shown on one screen. Touch voltage limit can be selected for 25V or 50V depending on application.

Earth Measurement
Using the classical Volt-Amper method with two auxiliary earth spikes and without external power source. All test leads and spikes are supplied as standard accessories.

Phase rotation
KEW 6016 can check the phase rotation of three phase lines with clear indication of the sequence on the display.

Voltage Measurement
In addiction to the voltage measurement, this function gives also the Frequency of the voltage under test.

 

 

Continuity
Range20/200/2000¥Ø (Auto-ranging)
 Open circuit
voltage (DC)
5V¡¾20% (*1)
Short circuit
current
Greater than 200mA
Accuracy ¡¾0.1¥Ø (0 - 0.19¥Ø)
¡¾2%rdg+8dgt (0.2 - 2000¥Ø) 
Insulation Resistance
Range20/200M¥Ø
(Auto-ranging)
20/200/2000M¥Ø (Auto-ranging)
Open circuit
voltage (DC)
250V+25% -0%500V+25% -0%1000V+20% -0%
Rated current1mA or greater
@ 250k¥Ø 
1mA or greater
@ 500k¥Ø
1mA or greater
@ 1M¥Ø
Accuracy¡¾2%rdg+6dgt
(0 - 19.99M¥Ø)
¡¾5%rdg+6dgt
(20 - 200M¥Ø)
¡¾2%rdg+6dgt (0 - 199.9M¥Ø)
¡¾5%rdg+6dgt (200 - 2000M¥Ø)
Loop Impedance
FunctionL-PEL-PE (ATT)L-N / L-L
Rated Voltage100 - 260V 50/60Hz
 
L-N: 100 - 300V
L-L: 300 - 500V
50/60Hz 
Nominal Test
Current at 0¥Ø
External Loop:
Magnitude/
Duration (*2)
20¥Ø: 6A/20ms
200¥Ø: 2A/20ms
2000¥Ø: 15mA/500ms
L-N: 6A/60ms
N-PE: 10mA/approx. 5s
20¥Ø: 6A/20ms
Range20/200/2000¥Ø
(Auto-ranging)
20/200/2000¥Ø
(Auto-ranging)
(L-N < 20¥Ø)
20¥Ø
Accuracy¡¾3%rdg+4dgt(*3)
¡¾3%rdg+8dgt(*4)
¡¾3%rdg+6dgt (*3)
¡¾3%rdg+8dgt(*4)
¡¾3%rdg+4dgt (*3)
¡¾3%rdg+8dgt(*4)  
PSC (L-N / L-L) / PFC (L-PE)
FunctionPSCPFCPFC (ATT)
Rated Voltage100 - 500V 50/60Hz100 - 260V 50/60Hz 
Nominal Test
Current at 0¥Ø
External Loop:
Magnitude/
Duration (*5)
6A/20ms6A/20ms
2A/20ms
15mA/500ms
L-N: 6A/60ms
N-PE: 10mA/approx. 5s 
 Range2000A/20kA Auto-Ranging
AccuracyPSC / PFC accuracy is derived from measured loop impedance
specification and measured voltage specification
RCD
FunctionX1/2X1X5Ramp Auto
Trip current
setting
10/30/100/300/
500/1000mA
10/30/
100mA   
10/30/
100/300/
500mA
Depending on the
accuracy at each
function.
Measurement sequence:
X1/2 0¡Æ¡æX1/2 180¡Æ
¡æX1 0¡Æ¡æX1 180¡Æ
¡æX5 0¡Æ¡æX5 180¡Æ
Measurements with
x5 are not carried out
for RCDs with
nominal current of
100mA or more.
Trip current
Duration
2000msG: 550ms
S: 1000ms
410msGoes up by
10% from
20% to
110%
G:300ms/
S:500ms
X10 times
Rated Voltage230V+10%-15% 50/60Hz
AccuracyAC Type:
-8% - -2%
A Type:
-10% - 0%
AC Type: +2% - +8%
A Type: 0% - +10%
AC Type: ¡¾4%
A Type: ¡¾10%
Trip time: ¡¾1%rdg+3dgt
RCD (Uc)
FunctionUC
Rated Voltage230V+10% - 15% 50/60Hz
Range100.0V
Test current¡Â 1/2I¥Än (max150mA)
Accuracy+5% - +15%rdg, ¡¾8dgt
Earth
Range20/200/2000¥Ø Auto-Ranging
Accuracy20¥Ø: ¡¾3%rdg+0.1¥Ø
200/2000¥Ø: ¡¾3%rdg+3dgt (Auxiliary earth resistance 100¡¾5%)
Phase Rotation
Rated Voltage50-500V 50/60Hz
RemarksCorrect phase sequence: are displayed "1.2.3" and  recycle mark
Reversed phase sequence: are displayed "3.2.1" and  recycle mark
Volts
FunctionVoltsFrequency
Rated Voltage25 - 500V, 45 - 65Hz
Measuring range 25 - 500V45 - 65Hz
Accuracy¡¾2%rdg+4dgt¡¾0.5%rdg+2dgt
Applicable standardsIEC 61010-1 CAT III 300V (500V L to L) Pollution degree 2, IEC 61010-031,
IEC 61557-1, 2, 3, 4, 5, 6, 7, 10, IEC 60529 (IP40), IEC 61326 (EMC)
Power sourceLR6 X 8
Dimensions136(L) X 235(W) X 114(D)mm
Weight1350g (including batteries.)
Included Accessories7188A (Distribution board fuse test lead set)
7196A (Test leads with remote control switch)
7218A (Power cord [EU]) (*6)
7228A (Earth resistance test leads)
8032 (Auxiliary earth spikes)
8212-USB (USB adaptor with KEW Report (Software))
9142 (Carrying case)
9121 (Shoulder strap)
Cord case, Buckle, Battery, Instruction manual
Optional Accessories8212-RS232C (RS232C adaptor with KEW Report (Software))

(*1): Voltages are output when measurement resistance is under 2100 ohm.
(*2): at 230V
(*3): 230V+10%-15%
(*4): voltages except for (*3)
(*5): at 230V
(*6): 7187A (Power cord [UK]), 7221A (Power cord [SA]), 7222A (Power cord [AU])

Accessories/Optional Accessories /Related Products