À̹ÌÁö detail
Residual Current Device Tester (KYORITSU/5406A), 500mA/0.6%
  • Á¦Á¶»çKYORITSU
  • ¸ðµ¨¸í5406A
  • ÁÖ¿ä±â´É ´©¼³Àü·ùÃøÁ¤, ´©Àü Â÷´Ü±â ½ÃÇè
»óÇ°»ó¼¼Á¤º¸

 

 

 

 

RCD Testers

MODEL 5406A

 

MODEL 5406A
CE
• Custom microprocessor controlled for highest accuracy and reliability.
• 3 LEDs for checking correct wiring status.
• 0 and 180 degree phase angle switch permits quick tests and consistent readings.
• Digital read-out of tripping time.
• Constant current source circuitry ensures that a fluctuating mains voltage does not affect the accuracy of readings.
• Large custom digital display readout.
• Visual indication of reversed phase and neutral wiring at socket.
• Designed to IP54 Rating.
• Complies with IEC 61557
• Test of a large kind of RCD's: Standard, Selective, AC and A (DC sensitive breakers)
Rated Tripping Current10/20/30/200/300/500mA
Fault Condition Settings¡¿ 1/2, ¡¿ 1, ¡¿ 5, ¡¿ DC,
AUTO RAMP
Trip Current Duration1000ms, 200ms (¡¿5)
Lowest Resolution1ms
Trip Time Accuracy¡¾0.6%rdg¡¾4dgt
Operating Voltage230V+10%-15%
(195V - 253V) 50Hz
Safety StandardIEC 61557-1,-6
IEC 61010-1 CAT III 300V
IEC 61010-2-031 Pollution Degree 2
Withstand Voltage3700V AC for 1 minute
IP RatingIEC 60529-IP54
Dimensions167(L) ¡¿ 186(W) ¡¿ 89(D)mm
Weight800g approx.
AccessoriesMolded plug test leads
Pouch for test leads
9121 (Shoulder Strap)
Instruction Manual
Optional7121B (Simplified measurement probe)